Assembly 7:
Steel-Framed Wall with Adhered Masonry Veneer

Assembly 7:
Steel-Framed Wall with Adhered Masonry Veneer

General Info

The Chapter 7 assembly is a rainscreen design approach with steel-framed wall structure and adhered masonry veneer. The components of this assembly, from interior to exterior, are shown in Fig. 7-1. This assembly is appropriate for many applications including low- or mid-rise residential or commercial buildings. An example application of this assembly is shown in Fig. 7-2. Benefits and special considerations for this assembly are discussed in Table 7-1.

Building Enclosure Control Functions and Critical Barriers

As noted in the Introduction, an above-grade wall assembly should provide control of water, air, heat, vapor, sound, and fire to serve as an effective and durable environmental separator. Control of these elements is provided by critical barriers such as a water-shedding surface (WSS), water-resistive barrier (WRB), air barrier system (AB), thermal envelope, and vapor retarder (VR). Refer to Fig. i-8 of the introductory chapter for a list of primary building enclosure control functions and associated critical barriers.

Fig. 7-3 illustrates the critical barrier locations for this assembly. The critical barriers for typical Chapter 7 assembly details are also provided adjacent to each detail at the end of this chapter.

As shown in Fig. 7-3, the WSS critical barrier occurs at the adhered masonry veneer, with most watershedding occurring at the wall face while a minimal amount of water will be stored within the masonry veneer to be released at a later time. The WRB and AB critical barriers occur at the same location exterior of the wall sheathing. As a result, a single membrane is typically used to provide these two critical barriers and is commonly referred to in this chapter as the air and water-resistive barrier (AB/WRB). The thermal envelope includes the exterior insulation and wall cavity insulation. The VR layer is located at the interior (warm side) of the steel-framed structure.

The following sections provide more information and discuss best practices for critical barriers specific to this assembly.

Water‑Shedding Surface (WSS)

The WSS is a critical barrier that controls water.

The adhered masonry veneer cladding, including both grout joints and masonry veneer units, is the primary WSS of this assembly. Additional components include sheet-metal flashings and drip edges, sealant joints, and fenestration systems as shown on the details included at the end of this assembly chapter.

To promote water-shedding at the masonry cladding, grouted joints between veneer units should be appropriately installed with a tooled concave (preferred) or “V” shape.

When finished, the WSS critical barrier should be free of gaps, except where providing drainage. Movement joints and joints around fenestrations and penetrations should be continuously sealed with a backer rod and sealant joint or counterflashed with a sheet-metal flashing to deflect wind-driven rain and shed water away from the rainscreen cavity.

Water‑Resistive Barrier (WRB)

The water-resistive barrier is a critical barrier that controls liquid water.

In this assembly, the WRB is a fluid-applied or self-adhered sheet membrane (that also functions as the AB). Either a fluid-applied or self-adhered sheet-applied membrane is depicted in the details at the end of this chapter. An example of a self-adhered sheet membrane is shown in Fig. 7-4. The AB/WRB membrane of this assembly may be designed as:

  • Vapor-permeable regardless of the amount of insulation within the cavity or exterior of the AB/WRB critical barrier.
  • Vapor-impermeable when at least 1/2 to 2/3 the total nominal insulation R-value of the assembly is placed exterior of the AB/WRB membrane. Note that where a vapor-impermeable membrane is used, it will also become the VR critical barrier. As a result, a separate VR critical barrier, as discussed at the interior side of the framing, should be omitted.

Refer to the introductory chapter for a discussion on the physical properties of both vapor-permeable and vapor-impermeable membranes.

The AB/WRB layer must be continuous across the wall face to serve as an effective critical barrier. In addition to the AB/WRB field membrane, the WRB critical barrier also includes fluid-applied or flexible flashing membranes, sealants, sheet-metal flashings, and interfaces with fenestration systems (e.g., windows and doors) as shown in the detail drawings that follow this chapter discussion. Where sheet-metal flashing components occur, the back leg of the sheet-metal flashing is lapped into the AB/WRB field membrane to encourage water at the WRB layer to drain toward the building exterior.

Cladding support clip fasteners in this assembly will penetrate the AB/WRB critical barrier and should be detailed based on the WRB manufacturer’s installation requirements. Typically, cladding support clips may be required to be set in a compatible sealant, fluid-applied flashing product, or attached through a self-adhered membrane patch.

Air Barrier (AB)

The air barrier is a critical barrier that primarily controls air, heat, and vapor. The AB also controls water, sound, and fire.

In this assembly, the AB system critical barrier is the same self-adhered sheet- or fluid-applied field membrane that also serves as the WRB critical barrier. The components described in the above Water-Resistive Barrier (WRB) section are also part of the AB layer, except sheet-metal flashings.

Fig. 7-4 Self-adhered sheet AB/WRB field membrane with fluid-applied rough opening detailing and exterior semi-rigid mineral fiber insulation.

Fig. 7-4 Self-adhered sheet AB/WRB field membrane with fluid-applied rough opening detailing and exterior semi-rigid mineral fiber insulation.

Thermal Envelope

The thermal envelope is a critical barrier that controls heat and assists with controlling vapor, sound, and fire.

In this wall assembly, the cavity and exterior insulation provide the thermal envelope. At transition details, the thermal envelope also includes exterior insulation across headers and floor lines, parapet cavity insulation, and insulation at the roof assembly, slab and foundation elements. Windows and doors that penetrate this wall are part of the thermal envelope.

Additional thermal envelope discussion is provided in the Thermal Performance and Energy Code Compliance section of this chapter and the introductory chapter.

Insulation Selection

The cavity insulation in this assembly is typically a vapor-permeable fiberglass or mineral fiber batt insulation product.

The exterior insulation typically used in this assembly is semi-rigid mineral fiber board insulation (R-4.2/inch), which is hydrophobic, tolerates moisture, and has free draining capabilities. Its vapor permeance allows it to be acceptable for use exterior of a vapor permeable AB/WRB membrane. An example of this insulation is shown in Fig. 7-4. The semi-rigid properties of the insulation allow it to be fit tightly around penetrations such as cladding support clips. A vapor-impermeable rigid board insulation such as XPS or moisture-resistant polyisocyanurate may be appropriate when a vapor-impermeable AB/WRB membrane is used. Refer to the Water-Resistive Barrier section of this chapter for discussion regarding AB/WRB permeability.

Vapor Retarder (VR)

The VR critical barrier is a layer that retards or greatly reduces (e.g., vapor barrier) the flow of water vapor due to vapor pressure differences across enclosure assemblies. Unlike the other critical barriers presented in this guide, the VR is not always necessary or required to be continuous.

When a vapor-permeable AB/WRB critical barrier is used within this assembly (see the Water-Resistive Barrier section of this chapter), the VR of this assembly is located on the interior (warm side) and is typically at the face of or just behind the interior gypsum board. The VR for this assembly should comply with Section 1405.3 of the governing International Building Code (IBC). In the Northwest, typical VR products include PVA vapor-retarding primer, asphalt-coated kraft paper, or a polyamide film retarder membrane. These products are discussed further in the introductory chapter.

When a vapor-impermeable membrane is used for the AB/WRB critical barrier (see the Water-Resistive Barrier (WRB) section of this chapter), the VR critical barrier is the AB/WRB membrane, and a separate VR membrane should not be used within this assembly.

Although masonry is defined as a noncombustible cladding material, the use of a combustible air and water-resistive barrier or foam plastic insulation within a wall cavity can trigger fire propagation considerations and requirements. Depending on the local jurisdiction, IBC Section 1403.5 regarding vertical and lateral flame propagation as it relates to a combustible water-resistive barrier may require acceptance criteria for NFPA 285. The use of foam plastic insulation within a wall cavity should also be addressed for IBC Chapter 26 provisions.

Drainage, Ventilation, and Water Deflection

The adhered veneer cladding is expected to shed most water exposure; however, some moisture is expected to penetrate the cladding and enter the rainscreen cavity. This moisture is drained through the cavity created by the continuous Z-girts that support the cladding and through the drainable, semi-rigid insulation.

Drainage and Ventilation

The rainscreen cavity is created by a 1-inch minimum continuous Z-girt typically spaced at 16 inches on-center to match the wall framing. These Z-girts should be broken at horizontal movement joints or where cross-cavity sheet-metal flashings occur; typically at every floor line for structures 3 stories or taller.

The rainscreen cavity should be open at the top and bottom to encourage ventilation and should be protected with an insect screen. This can be achieved by wrapping the insulation and base of the Z-girt. Insect screen should be placed at all locations where the rainscreen cavity is open to the exterior (e.g., base of walls, window head flashings, parapets, and cross-cavity flashings at floor lines).

Sheet-Metal Components

Sheet-metal components for this assembly are reflected throughout the details located at the end of this chapter. Cross-cavity sheet-metal components are located at the head of a penetration (e.g., a window head) and at cross-cavity floor line locations similar to that shown in Fig. 7-10. These flashings assist with draining the rainscreen cavity. Counterflashing sheet-metal components assist with watershedding and are located at window sills and parapet caps to protect the cavity from water ingress while still allowing for cavity ventilation.

Sheet-metal flashing components that bridge the exterior insulation degrade the thermal performance of the assembly; however, they are a necessary element for the rainscreen design approach.

Refer to the introductory chapter for general recommendations on sheet-metal flashing products, including design considerations and materials.

Fig. 7-10 Fiberglass clip with continuous Z-furring, semi-rigid insulation, and prefinished cross-cavity sheet-metal flashing.

Fig. 7-10 Fiberglass clip with continuous Z-furring, semi-rigid insulation, and prefinished cross-cavity sheet-metal flashing.

Movement Joints

In this assembly, the thin masonry units are bonded to a crack isolation membrane over cement backer board. If using clay masonry units, they will expand over time, whereas manufactured concrete veneer products and grout joints between units will shrink. Movement of the thin masonry veneer is accommodated within the grout, cement backer board, and crack isolation membrane.

The cement backer board and cladding support system as well as the steel framing are expected to experience some movement; as a result, both horizontal and vertical movement joints are recommended to allow for some differential movement between the structure, cladding support system, and veneer.

Horizontal gaps within the veneer and cladding support system should be provided at every floor line for buildings taller than three stories. These gaps are typically provided at cross-cavity sheet-metal flashing locations and should be continuous across the elevation of the building. Gaps above and below penetrations (such as windows) and below structure projections (such as parapet blocking) should also be provided. Locations where this gap should occur are indicated with an asterisk (*) in the details at the end of this chapter. Either a backer rod and sealant joint or through-wall sheet-metal flashing should be placed at each horizontal gap. The sizing and location of vertical movement joints will vary depending on the expected differential movement between the wall and veneer. It is the Designer of Record’s responsibility to appropriately locate and size each joint. In general, a minimum gap dimension of 3/8 of an inch should be provided.

Vertical joint recommendations vary throughout the industry and should be confirmed with the veneer unit manufacturer for the project-specific application. This guide recommends that vertical movement joints are located throughout the veneer system and that horizontal-to-vertical placement relationships are also considered. Refer to the Joint Location section of the introductory chapter for more information on locating joints. For vertical joints, a minimum gap dimension of 3/8 of an inch should be provided.

Structural Considerations

Adhered masonry veneers rely on adhesive to secure the masonry units and should be designed to comply with local building codes and ACI 530.

The code requires that adhered veneers be applied over concrete or masonry backings and, traditionally, adhered masonry was applied directly over these wall types. However, recent code cycles requiring exterior insulation have dictated that adhered veneers over steel stud framed walls include some insulation at the exterior face of the framed wall and water barrier.

Steel framing in this assembly is recommended to be 20 gauge or heavier, spaced at a maximum of 16 inches on-center and designed to limit the out-of-plane deflection of the wall to less than L/360 to reduce cracking in the veneer. Relative to other wall types, metal stud framing is relatively flexible, and stiffness rather than strength may be a controlling factor in the wall design. Fasteners used to secure cladding support clips through the exterior sheathing and back to the metal stud framing are recommended to be stainless steel, self-tapping, minimum #10 self-tapping screws (0.190-inch shank diameter). Fasteners should penetrate through the stud a minimum of 3/8 of an inch. Steel stud base metal thickness should be a minimum of 0.043 inches to prevent fastener pull-out.

Adhesion between adhered veneer units and the backer board must have a minimum shear strength at of at least 50 psi in accordance with ASTM C482. The units should be adhered in a thin-set mortar adhesive application to form a continuous bed free of voids. It is best practice to adhere veneer units with a modified mortar adhesive over a crack isolation membrane and water-resistive cement backer board.

When exterior insulation is required, the adhered veneer assembly is supported by intermittent cladding supports and continuous vertical Z-girts as shown in Fig. 7-11. The spacing of the supports and the sizing of the girts will need to be designed by the Designer of Record to resist building loads and limit out-of-plane deflection of the wall to less than L/360. Limiting this deflection will reduce the likelihood of flexural cracking. Minimizing the cladding support spacing may be considered to limit out-of-plane deflection but should be considered for impact on the effective thermal performance of the assembly. As shown in Fig. 7-12, smaller cladding support clip spacing is required to resist greater wind loads. As clip spacing is reduced, the effective thermal performance of the assembly is also reduced. Using lower conductivity structural supports can reduce the impact of cladding support clips.

Corrosion Resistance

To avoid premature cladding replacement, the durability and longevity of metal components within this assembly should match that expected of the masonry veneer cladding system. Metal components within this assembly include intermittent Z-girts (when constructed of metal), continuous Z-furring, sheet-metal flashings, and fasteners such as screws and anchors. Where available, metal components should be manufactured of Type 304 or 316 stainless steel, which is non-staining, resistant to the alkaline content of mortar materials, and tolerant of the high humidity conditions that can exist within a rainscreen cavity. Where stainless steel components may not be available, minimum G185 hot-dipped galvanized products should be considered.

Whereas the use of stainless steel sheet-metal flashing components is not always economically feasible or aesthetically desirable, prefinishing sheet metal may be considered. Where used, the base sheet metal should receive a minimum G90 hot-dipped galvanized coating in conformance with ASTM A653 or minimum AZ50 galvalume coating in conformance with ASTM A792. The exposed top finish of the sheet metal should be coated with an architectural-grade coating conforming to AAMA 2605.

Cement Backer Board

Cement backer board used within this assembly should be exterior-grade water-, mold-, and mildew-resistant, which meets ASTM C1325 Type A (exterior applications). The cement backer board, as shown in Fig. 7-13, should be attached to the continuous vertical Z-girts as required by the backer board manufacturer and project-specific design loads. The attachment method used should be appropriate for the Z-furring and intermittent cladding support design.

Joints of the cement board should be staggered and treated with a mesh tape bed in the veneer bonding material. Cement backer board product should be installed in conformance with the manufacturer installation instructions and set to provide a maximum 1/4-inch/10 feet tolerance. The cement backer board should not span joints within veneer that are expected to accommodate movement or crack control.

Fig. 7-13 Cement backer board installed over exterior insulation and cladding support system.

Fig. 7-13 Cement backer board installed over exterior insulation and cladding support system.

Crack Isolation Membrane

A crack isolation membrane is a flexible fluid-applied membrane used in thin masonry veneer applications where the veneer is adhered to a cement backer board. The crack isolation membrane is applied following installation of the cement backer board and treatment of the board joints. This membrane assists with:

  • Reducing veneer cracking. The thin veneer adheres to the membrane, which allows the cement backer board to move independently of the veneer.
  • Reducing fastener corrosion risk. The membrane protects cement board fasteners from moisture held within the veneer and bond coat.
  • Reducing cement board exposure to moisture. The membrane reduces the moisture exchanged between the cement board and veneer bond coat and can increase the longevity of the board.
  • Reducing efflorescence. The membrane reduces the moisture exchanged between the cement board and veneer bond coat and may result in reduced efflorescence.

Traditionally, this membrane may have been installed to protect the primary structure from moisture exposure. However, in this rainscreen assembly, the crack isolation membrane is not a replacement for the AB/WRB membrane, which is located on the exterior face of the CMU wall.

It is best practice to use a crack isolation membrane over cement backer board in thin masonry veneer applications. Some manufacturers may require this membrane to achieve a warrantable cladding installation. A crack isolation membrane is shown in Fig. 7-14.

Fig. 7-14 Installation of masonry veneer over thinset adhesive mortar and crack isolation membrane.

Fig. 7-14 Installation of masonry veneer over thinset adhesive mortar and crack isolation membrane.

Masonry Veneer

There are several types of adhered masonry veneer products that may be used with this assembly. Those most typical within the Northwest include thin veneer brick units made of clay or shale or manufacturer stone masonry veneer units.
Thin veneer brick used for this assembly should comply with ASTM C1088 and should be exterior-grade. Manufacturer stone masonry veneer units should comply with ASTM C1670.

For thin-set applications over cement board, as shown in this assembly, modified mortars should (at-minimum) conform to ANSI A118.4.

Appropriate product selection of masonry veneer units and mortar materials is necessary to provide a durable and water-resistive cladding system. The veneer units, mortar bed, and joints, should also be installed in conformance with industry standard best practices, manufacturer requirements, and comply with ASTM C1780. The specifics of architectural characteristics and structural properties of the veneer system, including mortar and cladding support systems, should be designed and reviewed by a qualified Designer of Record.

Various industry resources are available to assist with veneer design and are listed in the Resources section.

Clear Water Repellents

A clear water repellent should be applied to the adhered masonry veneer of this assembly. Refer to the introductory chapter for more information on selecting an appropriate clear water repellent and best practice installation guidelines.

Details

Typical Window Head (Detail 7-A)

Assembly 7 Detail 7A Critical BarriersLEGEND

  1. Typical Assembly:
    – Interior gypsum board
    – VR
    – Steel-framed wall with batt insulation
    – Exterior gypsum sheathing
    – Vapor-permeable fluid-applied or self-adhered sheet AB/WRB field membrane
    – Semi-rigid mineral fiber insulation
    – Intermittent cladding support clip with 1-inch vertical Z-girt
    – Cement backer board
    – Crack isolation membrane
    – Adhesive thinset mortar
    – Adhered masonry veneer with grouted joints
    – Clear water repellent
  2. Fluid-applied or self-adhered sheet AB/WRB head prestrip membrane
  3. Sheet-metal head flashing with 1/2-inch hemmed drip edge and end dams beyond
  4. Insect screen
  5. Sealant over backer rod
  6. Window strap anchor, bed in AB sealant at sealant joint plane
  7. Non-flanged window
  8. AB sealant over backer rod, tied to continuous seal at window perimeter
    * Size joint for project-specific building movement and drainage, minimum 3/8-inch.

Detail Discussion

  • AB and WRB continuity is provided by the fluid-applied or self-adhered sheet AB/WRB field membrane, AB/WRB head prestrip membrane, and AB sealant transition to the window. Window strap anchors are bed in sealant during fastening to eliminate an AB discontinuity behind the strap anchor that would otherwise lead to both air leakage and water ingress.
  • A non-flanged window is used here. It facilitates future window repair and replacement without the need to remove the masonry veneer.
  • Intermittent cladding support clips (beyond) may need to be bed in sealant, fluid-applied flashing membrane, or attached through self-adhered flexible membrane patches per AB/WRB manufacturer recommendations when fastening to the steel-framed structure. This ensures both airtightness and watertightness where the fasteners penetrate the AB/WRB field membrane.

Assembly 7 Detail 7A

Typical Window Sill (Detail 7-B)

Assembly 7 Detail 7B Critical BarriersLEGEND

  1. Typical Assembly:
    – Interior gypsum board
    – VR
    – Steel-framed wall with batt insulation
    – Exterior gypsum sheathing
    – Vapor-permeable fluid-applied or self-adhered sheet AB/WRB
    – Semi-rigid mineral fiber insulation
    – Intermittent cladding support clip with 1-inch vertical Z-girt
    – Cement backer board
    – Crack isolation membrane
    – Adhesive thinset mortar
    – Adhered masonry veneer with grouted joints
    – Clear water repellent
  2. Non-flanged window on minimum 1/4-inch intermittent shims
  3. Sealant over bond breaker
  4. Insect screen
  5. Sheet-metal sill flashing with 1/2-inch hemmed drip edge. End dam beyond. Attach to intermittent L-angle at window per window manufacturer recommendations.
  6. Fluid-applied AB/WRB sill membrane (or flexible self-adhered flashing membrane)
  7. Continuous AB sealant, tied to continuous seal at window perimeter
  8. Back dam angle, minimum 1-inch tall, with window fastened through back dam angle per window manufacturer recommendations.

Detail Discussion

  • AB and WRB continuity is provided by the fluid-applied or self-adhered sheet AB/WRB field membrane, AB/WRB sill membrane, and AB sealant transition to the window.
  • The sheet-metal sill flashing conceals the rainscreen cavity. Terminate the sill flashing with end dams at each jamb. Counterflash each end dam with the sheet-metal jamb trim to close off the rainscreen cavity and complete the WSS.
  • Intermittent shims below the window encourage drainage of the window rough opening into the rainscreen cavity.

Assembly 7 Detail 7B

Typical Window Jamb (Detail 7-C)

Assembly 7 Detail 7C Critical BarriersLEGEND

  1. Typical Assembly:
    – Interior gypsum board
    – VR
    – Steel-framed wall with batt insulation
    – Exterior gypsum sheathing
    – Vapor-permeable fluid-applied or self-adhered sheet AB/WRB
    – Semi-rigid mineral fiber insulation
    – Intermittent cladding support clip with 1-inch vertical Z-girt
    – Cement backer board
    – Crack isolation membrane
    – Adhesive thinset mortar
    – Adhered masonry veneer with grouted joints
    – Clear water repellent
  2. Non-flanged window
  3. Sealant over backer rod
  4. Fluid-applied or self-adhered sheet AB/WRB jamb prestrip membrane
  5. Sheet-metal jamb trim bed in sealant at masonry veneer and counterflashed over sill flashing end dams below. Attach trim to nearest vertical Z-girt as shown.
  6. Intermittent cladding support clip with 1-inch vertical Z-girt
  7. Continuous AB sealant, tied to continuous seal at window perimeter
  8. Window strap anchor, bed in AB sealant at sealant joint plane

Detail Discussion

  • AB and WRB continuity is provided by the fluid-applied or self-adhered sheet AB/WRB membrane, the AB/‌WRB jamb prestrip membrane, and the AB sealant transition to the window.
  • Where needed, the exterior insulation should be supported with intermittent fasteners such as mechanically attached impaling pins. Consult with the AB/WRB manufacturer for requirements on detailing these pin attachments through the plane of the AB/WRB field membrane.

Assembly 7 Detail 7C

Typical Floor Line (Detail 7-D)

Assembly 7 Detail 7D Critical BarriersLEGEND

  1. Typical Assembly:
    – Interior gypsum board
    – VR
    – Steel-framed wall with batt insulation
    – Exterior gypsum sheathing
    – Vapor-permeable fluid-applied or self-adhered sheet AB/WRB
    – Semi-rigid mineral fiber insulation
    – Intermittent cladding support clip with 1-inch vertical Z-girt
    – Cement backer board
    – Crack isolation membrane
    – Adhesive thinset mortar
    – Adhered masonry veneer with grouted joints
    – Clear water repellent
  2. Insect screen, typical
  3. Sheet-metal flashing with 1/2-inch hemmed drip edge and end dams
    * Size joint for building movement, minimum 3/8-inch separation for building movement, drainage, and ventilation.

Detail Discussion

  • The cross cavity sheet-metal flashing conceals the rainscreen cavity from debris and wind‑driven rain, while still allowing ventilation.
  • Space above and below the cross cavity sheet-metal flashing is necessary to allow for relative movement between the structure and veneer.

Assembly 7 Detail 7D

Typical Parapet at Inverted Roof Membrane System (Detail 7-E)

Assembly 7 Detail 7E Critical BarriersLEGEND

  1. Parapet Assembly
    – Interior gypsum board
    – VR
    – Steel-framed wall with batt insulation
    – Exterior gypsum sheathing
    – Vapor-permeable fluid-applied or self-adhered sheet AB/WRB field membrane
    – Semi-rigid mineral fiber insulation
    – Intermittent cladding support clip with 1-inch vertical Z-girt
    – Cement backer board
    – Crack isolation membrane
    – Adhesive thinset mortar
    – Adhered masonry veneer with grouted joints
    – Clear water repellent
  2. Inverted roof membrane assembly
  3. Standing-seam sheet-metal coping with gasketed washer fasteners
  4. Preservative-treated blocking
  5. High-temperature self-adhered membrane
  6. Insect screen
  7. Closed-cell spray foam insulation plug (AB)
    * Size joint for building movement, minimum 3/8-inch separation for building movement, drainage, and ventilation.

Detail Discussion

  • The sheet-metal parapet cap with hemmed drip edge is held off the adhered masonry veneer face to promote ventilation through the rainscreen cavity.
  • A insect screen around the insulation and vertical Z-girt cavity prevents insects and debris from entering the rainscreen cavity, while still allowing ventilation.

Assembly 7 Detail 7E

Parapet Assembly Cutaway Section (Detail 7-F)

LEGEND

  1. Steel-framed wall with batt insulation
  2. Exterior gypsum sheathing
  3. Steel-framed parapet framing
  4. Closed‑cell spray foam insulation plug (AB)
  5. Preservative‑treated blocking
  6. Inverted roof membrane assembly
  7. Vapor-permeable fluid-applied or self-adhered sheet AB/WRB field membrane
  8. Fluid-applied or self-adhered sheet AB/WRB head and jamb prestrip membrane
  9. Non-flanged window
  10. Sheet-metal head flashing with 1/2‑inch hemmed drip edge and end dams
  11. Fluid-applied or self-adhered sheet AB/WRB field membrane
  12. High-temperature self-adhered membrane
  13. Standing seam sheet-metal coping with gasketed washer fasteners
  14. Intermittent cladding support clips with 1-inch vertical Z-girt
  15. Semi-rigid mineral fiber exterior insulation
  16. Cement backer board
  17. Crack isolation membrane
  18. Adhesive thinset mortar
  19. Adhered masonry veneer with grouted joints

3-D Detail Discussion

  • Three-dimensional cutaway sections on the next three pages represent two-dimensional details of this assembly.
  • In all details, WRB and WSS elements are shingle-lapped to encourage water shed in both the rainscreen cavity and at the adhered masonry veneer face.
  • As shown in Detail 7-F and Detail 7-G, exterior insulation fits between the intermittent cladding supports clips. If using rigid board insulation, the insulation may require notching around clips. Where needed, the exterior insulation should be supported with intermittent fasteners such as mechanically attached impaling pins. Consult with the AB/WRB manufacturer for detailing requirements where impaling pins are attached through the AB/WRB field membrane.
  • End dams are formed at the ends of the sheet-metal head flashing shown in Detail 7-F to direct water away from the rainscreen cavity and back to the exterior.

Assembly 7 Detail 7F

Floor Line Cutaway Section (Detail 7-G)

LEGEND

  1. Steel-framed wall with batt insulation
  2. Exterior gypsum sheathing
  3. Vapor-permeable fluid-applied or self-adhered sheet AB/WRB field membrane
  4. Sheet-metal cross cavity flashing with 1/2-inch hemmed drip edge and end dams
  5. Vapor-permeable fluid-applied or self-adhered sheet AB/WRB field membrane
  6. Fluid-applied or self-adhered sheet AB/WRB head and jamb prestrip membrane
  7. Non-flanged window
  8. Sheet-metal sill flashing with 1/2-inch hemmed drip edge and end dams
  9. Exterior semi-rigid mineral fiber insulation and intermittent cladding support clip with 1-inch vertical Z-girt
  10. Adhered masonry veneer with grout joints over adhesive thinset mortar, crack isolation membrane, and cement backer board

Assembly 7 Detail 7G

Window Jamb / Sill Cutaway Section (Detail 7-H)

LEGEND

  1. Continuous back dam angle across sill, minimum 1 inch tall, with window fastened through back dam angle per window manufacturer recommendations
  2. Vapor-permeable fluid-applied AB/WRB field membrane
  3. Fluid-applied or flexible self-adhered AB/WRB sill flashing membrane
  4. Intermittent minimum 1/4-inch shims
  5. Continuous AB sealant, tied to continuous seal at window perimeter
  6. Non-flanged window
  7. Continuous AB sealant over backer rod
  8. Sheet-metal sill flashing with 1/2-inch hemmed drip edge and end dams
  9. Sealant over bond breaker
  10. Intermittent cladding support clips with 1-inch vertical Z-girt
  11. Exterior insulation semi-rigid insulation
  12. Adhered masonry veneer with grout joints over adhesive thinset mortar, crack isolation membrane, and cement backer board

Assembly 7 Detail 7H

Specifications

Thermal Modeling

Thermal Performance and Energy Code Compliance

This chapter assembly is typically classified as a “metal-framed” above-grade wall for energy code compliance purposes. Prescriptive energy code compliance values for this assembly are summarized in Table 7-2 and describe:

  • Minimum insulation R-values for a prescriptive R-value compliance strategy.
  • Maximum assembly U-factors for a prescriptive U-factor alternative compliance strategy. Note, the equivalent assembly effective R-value of this maximum U-factor has been calculated and is denoted in parenthesis ( ) for easy comparison to thermal modeling results included within this chapter.

For cavity insulation, steel-stud walls are typically constructed with 16-inch on-center stud spacing and can accommodate up to an R-15 batt insulation for 4-inch studs or R-21 batt insulation for 6-inch studs. Alternate insulation products may also be used to fill the cavity but are not discussed within this guide. Steel framing, because of its high thermal conductivity properties, can reduce the nominal thermal performance of the stud cavity insulation by approximately 40 to 60%. For this reason, continuous insulation is necessary for prescriptive energy code compliance.

When a non-prescriptive compliance option (e.g., a trade-off strategy or whole-building modeling strategy) is used for energy code compliance, this assembly’s effective thermal performance will need to be calculated; however, it may or may not be required to meet the prescriptive values shown in Table 7-2.

Fig. i-17 of the introductory chapter describes the typical process of navigating energy code compliance strategies and options. Thermal modeling results demonstrated within this chapter may be used to assist with estimating insulation thickness and cladding support clip type/material to achieve a target thermal performance value. Options for thermally optimizing this assembly, as determined through the modeling results are also provided.

Assembly Effective Thermal Performance

Claddings support clips, such as intermittent Z-girts or fiberglass clips as shown in Fig. 7-5, penetrate the exterior insulation in this assembly and create areas of thermal bridging (i.e., heat loss). An example of the thermal bridging is described by Fig. 7-6 and Fig. 7-7, which show the relative thermal gradient of this assembly when thermally modeled with an intermittent Z-girt. The lighter blue thermal gradient color at the attachment describes a warmer temperature than the adjacent darker blue insulation face—an indicator of heat loss at the penetration through the insulation. This thermal bridging reduces the assembly’s effective thermal performance.

Three-dimensional thermal modeling demonstrates this assembly’s effective thermal performance with various insulation thicknesses, insulation R-values, and cladding support clips. A discussion on the modeling performed for this guide is included in the Introduction Chapter and the Appendix.

Thermal Modeling: Variables

The following are modeling variables specific to this assembly—steel-framed wall with adhered masonry veneer:

  • Framing and Cavity Insulation: 3 5/8-inch steel stud wall with R-15 batt insulation. A full-height steel-stud wall including the top and bottom track adjacent to a concrete slab, but do not include the wall area at the slab edge.
  • Cladding Supports, Clips, and Fasteners, where applicable: Two example cladding support systems are considered and are shown in Fig. 7-5:
    Intermittent Z-girts (16-gauge) made of either stainless steel or galvanized steel. Clips are 6 inches tall and spaced at 24 inches on-center vertically, 16 inches on-center horizontally.

    • Fiberglass standoff clips spaced at 24 inches on-center vertically and 16 inches on-center horizontally. Both stainless steel and galvanized steel fasteners are considered for the fiberglass clip option.
  • Exterior Insulation: R-4.2/inch or R-6/inch insulation product in thicknesses of 2, 3, and 4 inches. The R-values selected demonstrate the lower and upper thermal resistance of typical exterior insulation products.

Thermal Modeling: Results

The results of this modeling are shown in Table 7-3, Fig. 7-8, and Fig. 7-9 (see page 7-10 and page 7-11) and demonstrate the assembly effective R-value under various conditions; Fig. 7-8, and Fig. 7-9 are graphical representations of the results summarized in Table 7-3. Discussion of these results is provided below and key points for thermally optimizing this assembly are italicized in boldface.

  • When comparing the same insulation thickness for the fiberglass clips and intermittent Z-girts, Table 7-3 results demonstrate that fiberglass clips will reduce the assembly’s effective R-value for Cavity + Exterior Insulation (Without Penetrations) by 10 to 29%, while intermittent Z-girts will reduce the performance by 16 to 24%. Thermally improved cladding attachment options can achieve better effective thermal performance values. A number of systems are commercially available and new products continue to be developed. Most manufacturers of proprietary clip systems will have thermal modeling results available for use in determining the assembly’s thermal performance for energy code compliance.
  • As determined from Table 7-3, when comparing the same insulation thickness for the fiberglass clips the assembly’s effective R-value for Cavity + Exterior Insulation (Without Penetrations) is reduced by 10 and 17% for stainless steel fasteners and 18 and 29% for galvanized steel fasteners. Stainless steel cladding attachment options yield better assembly effective R-values than galvanized steel fasteners.
  • Greater effective R-values occur for intermittent Z-girts made of stainless steel than for galvanized steel when comparing the same insulation thickness for the different Z-girt types in both Fig. 7-8, and Fig. 7-9. Overall, stainless steel Z-girts reduce the assembly’s effective R-value by 16 to 26%, while galvanized steel Z-girts reduce it by 26 to 42%. Intermittent Z-girts made of stainless steel perform better than galvanized steel.
  • Fig. 7-9 can be used to demonstrate how effective thermal performance and exterior insulation depth can help determine the best combination of the insulation and cladding support clip type/material. For example, if an effective R-24 is desired, the following options are described below. This exercise can help with determining the most cost-effective solution for reducing the wall thickness while meeting an energy performance target. This exercise can also help optimize effective thermal performance if a maximum exterior insulation thickness is known. Consider the selection of insulation and cladding support as a combination especially when wall thickness is important.
    • 3 inches (approx.) of R-6/inch insulation with fiberglass clips and stainless steel screws
    • 3.5 inches of R-6/inch insulation with intermittent stainless steel Z-girts
    • 4 inches (approx.) for R-6/inch insulation with fiberglass clips and galvanized steel fasteners or R-4.2/inch insulation with fiberglass clips and stainless steel fasteners

Project-specific thermal performance values for the opaque above-grade wall assembly of this chapter should be used for energy code compliance and should be determined from a source that is approved by the local governing jurisdiction. Sources may include the Appendices of the WSEC and SEC, ASHRAE 90.1, COMcheck, thermal modeling, or other industry resources.

Fig. i-17 Energy Code Compliance Flow Chart. Use this chart to navigate selection of an energy code compliance strategy and use of the modeling results within this guide.

Fig. i-17 Energy Code Compliance Flow Chart. Use this chart to navigate selection of an energy code compliance strategy and use of the modeling results within this guide.

Fig. 7-5 Cladding support clip options modeled include intermittent Z-girt (left) and fiberglass standoff clip (right).

Fig. 7-5 Cladding support clip options modeled include intermittent Z-girt (left) and fiberglass standoff clip (right).

Table 7-2 Assembly 7 prescriptive energy code compliance values excerpted from Table i-1 of the introductory chapter.

Table 7-2 Assembly 7 prescriptive energy code compliance values excerpted from Table i-1 of the introductory chapter.

Table 7-3 Assembly 7 thermal modeling results.

Table 7-3 Assembly 7 thermal modeling results.

Pricing Analysis

A pricing analysis for this assembly is provided on Table 7-4. Pricing demonstrates the relative price per square foot and is based on a 10,000-square-foot wall area with easy drive-up access. Pricing includes all components outboard of the exterior wall sheathing and provides no evaluation for interior finishes (including VR), framing/sheathing, or cavity insulation.

Pricing is valued for the 2015–2016 calendar year.

Table 7-4 Assembly 7 steel-framed wall with adhered masonry veneer pricing analysis.

Table 7-4 Assembly 7 steel-framed wall with adhered masonry veneer pricing analysis.